Cable Ampacity Chart

Maximum current-carrying capacity (ampacity) for copper and aluminium cables. Values at 30°C ambient temperature, reference installation method C (clipped direct). IEC 60364 / IEC 60228.

Material
Insulation
Category

Showing 19 of 19 conductor sizes

Copper values Aluminium values Not available / not applicable
Conductor
Size
Copper — PVC 70°C Copper — XLPE 90°C Aluminium — PVC 70°C Aluminium — XLPE 90°C Typical Application
Single (A) 3-Core (A) Single (A) 3-Core (A) Single (A) 3-Core (A) Single (A) 3-Core (A)
Reference Conditions Values are based on IEC 60364-5-52, reference installation method C (single cable clipped directly to a non-metallic surface) at 30°C ambient air temperature. For other installation methods, apply derating factors.
Temperature Derating Nigerian ambient temperatures typically reach 40°C. Apply a derating factor of 0.87 to PVC cable values and 0.90 to XLPE cable values when designing for standard Nigerian outdoor installations.
Grouping Derating When cables are grouped, further derating applies: 3 circuits = 0.70, 4–5 circuits = 0.60, 6–9 circuits = 0.53. Multiply the tabulated ampacity by the appropriate grouping factor.
Aluminium Conductors Aluminium conductors are not generally used below 4 mm² due to mechanical and termination constraints. For the same cross-sectional area, aluminium has approximately 61% of the conductivity of copper.